TROUBLE SHOOTING GUIDE
Air Supply / Ventilation Problems
Glass “Soot’s” Up At A Very Fast Rate,
Flame Is Lazy, Dark, And Has Black Tips ,
After Stove Has Been On For A While, The Burnpot
Over lls
Possible Causes: Possible Remedies: (Unplug Stove First When Possible)
EXHAUST / VENTILATION
There is a leak in the vent pipe system. Inspect all vent pipe connections. Make sure they are sealed
with RTV silicone that has a temperature rating on 500 degree f
or higher. Also, seal joints with ul-181-ap foil tape. Make sure
the square to round adapter piece on the combustion blower has
been properly sealed with the same rtv.
Vent pipe installed improperly. Check to make sure the vent pipe has been installed according
to the criteria in the owners manual.
Stove or vent pipe is dirty, which restricts air ow through the
burnpot.
Follow all cleaning procedure in the maintenance section of
the owners manual.
COMBUSTION AIR
The air inlet, or the interior chambers have a partial blockage. Follow all cleaning procedures in the maintenance section of
the owner's manual.
Blockage in air intake pipe. Visually inspect the air intake pipe that leads into the burnpot
for foreign material.
The rebox is not properly sealed. Make sure the door is closed and that the gasket is in good
shape.
AIR DAMPER
The air damper is too far open for a low feed setting. If on the low setting, you may need to close the damper all
the way.
Air damper is set too far closed for a higher setting. Pull the damper knob to the left and try to burn the unit again.
Air damper is broken. Visually inspect the damper assembly. Make sure the damper
plate is attached to the damper rod. When the damper rod is
moved, the plate should move with it.